Radiant Heating and Cooling:
The Holistic Approach to Energy Efficiency
Radiant heating and cooling systems are more energy efficient
compared to traditional forced air systems for several
reasons. But let's start at the building occupant since their
comfort is one of the main reasons we have the built
environment.
Thermal Comfort Benefit
There are six primary factors that affect thermal comfort (see
Figure 1). The use of a radiant heating and cooling system
has an effect on the radiant temperature, and air speed which can
allow for a wider range for the temperature set point of the
space. Instead of a seasonal temperature range of 72°F to
76°F with traditional forced air systems a radiant system could
provide thermal comfort with a seasonal temperature range of 68°F
to 80°F. This wider temperature range reduces the associated
heating and cooling energy needed which equates to annual energy
savings.
Figure 1 - Thermal Comfort Factors
click to enlargeHeat transfer
in a space occurs in three primary ways: Conduction, Convection,
and Radiation. With respect to subjective human comfort the
optimal split is about 60% by thermal radiation and 40% by thermal
convection. Since the body wants to lose most of its heat through
radiation a radiant heating and cooling system can provide a higher
perception of thermal comfort.
Low-Temperature Heating and High-Temperature
Cooling
Additional energy efficiency is gained due to the use of
low-temperature heating and high-temperature cooling. Since
the radiant floor does not want to be too hot or too cold for
comfort reasons, the heating and cooling supply water temperatures
operate at different set points compared to traditional
systems. The radiant heating and cooling system supply water
temperature would typically operate at a temperature less than
180°F for heating and greater than 45°F for cooling, which are
typical supply water temperatures for a traditional forced air
system. The central plant heating and cooling equipment can
operate more efficiently at these temperature set points. For
the radiant cooling system there is the added benefit of extending
the operating range of the water-side economizer.
Also, studies have shown that the use of indirect evaporative
cooling coupled with radiant cooling and a Dedicated Outdoor Air
System (DOAS) can have significant reductions in cooling season
energy costs when compared to traditional forced air variable air
volume (VAV) systems. This savings is estimated to be as high
as 67% when applied in the San Francisco, California area.
Ventilation Reductions
Since the radiant heating and cooling system serves the zone
level sensible heating and cooling loads the air side system is
only needed to provide for the ventilation requirements of the
space. In a typical office space the airflow required to cool
and ventilate the space can be 3 to 4 times greater than that
required to just ventilate the space. This allows the central
air handling system and associated distribution system to be
down-sized accordingly. A system called a Dedicated Outdoor
Air System (DOAS) is typically used to serve the ventilation needs
(see side bar for more info on DOAS).
The use of a DOAS also allows for the effective use of energy
recovery on the incoming outside air to further reduce the
associated heating and cooling ventilation loads. Localized
demand control ventilation can also be implemented to turn off the
ventilation air when the space is not occupied which further
reduces the total energy of the system. The efficiency gain
of this demand control ventilation strategy needs to be weighed
against the additional system complication and cost as well as the
additional fan energy related to the required air terminals.
This brings us to the distribution systems.
Distribution Energy
In traditional forced air systems the heating, cooling and
ventilation is provided by a central air handling unit and then
distributed to the required space by an air distribution
system. The volume of air required to heat and cool the space
is then a function of the energy carrying capacity of the fluid, in
this case air. With a radiant heating system the heating and
cooling energy is carried in water which has much more energy
capacity per volume than air. This reduces the distribution
energy needed to move the heating and cooling energy to the
occupied zones. Because there is more energy per volume, the
hydronic distribution system also requires less space than an air
distribution system. A typical hydronic zone distribution
header can be seen in Figure 2.
Figure 2 - Heating and Cooling Tubing in
NREL-RSF
click to enlarge
Photo: NRELAlso, the traditional air distribution system
has air terminal devices to modulate the heating and cooling
capacity to each individual space. These air terminals add
additional pressure drop and increase the associated fan
energy. With a DOAS the air terminals are not required for
proper operation of the system. The space saved by using a
DOAS can be used to install a low-static air-side distribution
system to further reduce the associated fan energy.
Additional Benefits
Not all of the benefits are associated with energy
savings. Some additional benefits beyond what were discussed
above are as follows:
- Reduced mechanical space requirements
- Lower maintenance costs
- Reduced commissioning cost
- Reduced system noise to occupied space
Summary
There are many ways a radiant heating and cooling system can
make a building more energy efficient compared to a traditional
forced air system. But alone the use of radiant heating and
cooling systems only achieve a small percentage of the potential
energy and cost savings. It takes a holistic approach to
optimize all of the different heating, ventilation and air
conditioning systems to fully realize all of the energy
savings.
| Training Highlights |
|
California utilities offer outstanding educational opportunities
that focus on the design, construction and operation of
energy-efficient buildings. Listed here are a few of the many
upcoming classes and events; for complete schedules, visit each
utility's website.
HVAC System Airflow and Static Pressure
Diagnostics
Participants in this hands-on class will use a full-size
horizontal HVAC system to measure system variables will include
different filters, coils, variable size return ducts, duct testing,
and different leakage amounts.
Thursday March 29, 9:00 am to 5:00 pm
EOC, Fresno
register>
|
The Passive House Approach to Zero Net Energy
Homes
This class will introduce the Passive House standard and
demonstrate its applicability to zero net energy homes, drawing on
experience with actual projects.
Tuesday April 3, 9:00 am to 4:30 pm
Pacific Energy Center, San Francisco
register >
Implementing Energy Efficiency Projects
Attendees will learn how to do a basic audit and determine if new
equipment is worth the investment.
Tuesday April 17, 8:30 am to 3:30 pm
Irvine City Hall
|
Don't miss future issues - to sign up for a free email subscription, please visit our
newsletter subscription page. Send letters to the editor, suggestions on topics for future
issues, or other comments to the e-News editor via our
Comments & Feedback form.
e-News is published by Energy Design
Resources (www.energydesignresources.com),
an online resource center for information on energy efficiency design practices in
California.
Savings By Design (www.savingsbydesign.com)
offers design assistance and incentives to design teams and building owners in California
to encourage high-performance nonresidential building design and construction.
Energy Design Resources and Savings By Design are funded by California utility customers
and administered by Pacific Gas and Electric Company, Sacramento Municipal Utility
District, San Diego Gas and Electric, Southern California Edison and Southern California
Gas Company, under the auspices of the California Public Utilities Commission.